Permit 2610365
4049 PEAK VIEW DR · Filed 2026-11-23
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Active |
| Work Done | A/C Hookup |
| Notes | AC Replacement |
| Owner | Johnny Tonko |
| Contractor | R BUCK HEATING, COOLING, PLUMBING & ELEC |
| Contractor Phone | 805-512-3738 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-11-23 03:23:00 | JVD | E14 - AC Final - Electrical | Rejected | Replaced an relocated an existing AC condensing unit. Verified smokes/COs and service receptacle. Corrections: 1. Strap the liquitite conduit within 12" of the AC disconnect. 350.30 and 356.30 2. Wirenuts used to join aluminum to copper in junction box must be listed for use with dissimilar metals. 110.14 |