Permit 2610049

1634 WEATHERBY LN · Filed 2026-11-16

Permit Details

TypeElectrical
Work Class003R Electrical Other | A/C Hookup
StatusHas Final
Work DoneA/C Hookup
NotesNew AC Electrical Hookup
OwnerIssac Torres
ContractorMAGNUM ELECTRIC INC.
Contractor Phone719-240-0952

Inspection History

DateInspectorTypeResultComment
2026-11-17 10:49:00 KJG E14 - AC Final - Electrical Rejected Installation of new ac unit. Reinspection fee required for 2nd trip. Corrections 1. Need service receptacle within 25' of ac unit. NEC 210.63 2. Need GFCI protection for ac unit. NEC 210.8 (F) 3. Need to identify ac breaker in panel. NEC 408.4 4. Install the smoke and carbon monoxide detectors per the IRC. IRC-R314 and R315 Missing smoke and/or co detectors outside bedrooms Note: hardwired smoke detectors look old and may need to be replaced.
2026-11-20 02:18:00 KJG E14 - AC Final - Electrical Final Corrections made per previous inspection notes. State variance on 210.8 (F)