Permit 2610049
1634 WEATHERBY LN · Filed 2026-11-16
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Has Final |
| Work Done | A/C Hookup |
| Notes | New AC Electrical Hookup |
| Owner | Issac Torres |
| Contractor | MAGNUM ELECTRIC INC. |
| Contractor Phone | 719-240-0952 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-11-17 10:49:00 | KJG | E14 - AC Final - Electrical | Rejected | Installation of new ac unit. Reinspection fee required for 2nd trip. Corrections 1. Need service receptacle within 25' of ac unit. NEC 210.63 2. Need GFCI protection for ac unit. NEC 210.8 (F) 3. Need to identify ac breaker in panel. NEC 408.4 4. Install the smoke and carbon monoxide detectors per the IRC. IRC-R314 and R315 Missing smoke and/or co detectors outside bedrooms Note: hardwired smoke detectors look old and may need to be replaced. |
| 2026-11-20 02:18:00 | KJG | E14 - AC Final - Electrical | Final | Corrections made per previous inspection notes. State variance on 210.8 (F) |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved November 23, 2026.