Permit 2609056
1327 BRAGDON AVE · Filed 2026-10-23
Permit Details
| Type | Mechanical |
|---|---|
| Work Class | 004R Mechanical Other | Replace Furnace |
| Status | Active - Flagged |
| Work Done | Replace Furnace |
| Notes | Furnace replacement |
| Owner | Justin |
| Contractor | PIKE HEATING & AIR LLC |
| Contractor Phone | 719-821-6723 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-10-23 10:46:00 | JJG | M18 - Furnace Final | Rejected | 1-need to replace gas flex connector, (manufacture specs, rated for one time use only), 2-need to install sediment trap as per manufacture specs, and IFGC 408.4 Sediment trap. 3-need to blank off opening into the building within 4' of vent termination, (manufacture specs, and IFGC Table 503.8 Trough the wall vent termination), 4-terminate vent according to manufacture specs, 5-support vent as per IMC Table 305.4 Piping Support Spacing) a $100 re-inspection fee will be assessed |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved October 24, 2026.