Permit 2608605
1636 LAKE AVE · Filed 2026-10-09
Permit Details
| Type | Plumbing |
|---|---|
| Work Class | 002R Plumbing Other | Water Line Repair/replacement |
| Status | Active - Flagged |
| Work Done | Water Line Repair/replacement |
| Notes | Underground waterline from meter to house |
| Owner | Aaron Marquez |
| Contractor | SUMMIT PLUMBING COMPANY LLC |
| Contractor Phone | 719-369-6888 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-10-09 09:54:00 | DJM | P04 - Water Line | Rejected | 48in MINIMUM DEPTH. Ordinance. Amen c. 305.4 Where main enters house Approved Material. Table 605.3 Use correct dresser coupling TRACER WIRE INSTALLED ON NON-METALLIC PIPE. State regulation. Must be grounded to galvanized pipe and tracer wire must go inside house. $100 reinspection fee added to permit for 2nd inspection that is required. |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved October 10, 2026.