Permit 2608420
1724 E 10TH ST · Filed 2026-10-05
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003 Electrical New | A/C HOOKUP 1 0 |
| Status | Active |
| Work Done | A/C HOOKUP 1 0 |
| Notes | RES ELEC TO HVAC |
| Owner | ROMERO |
| Contractor | SELF |
| Contractor Phone | N/A |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-10-05 10:28:00 | KJG | E14 - AC Final - Electrical | Rejected | Installation of new ac unit and furnace. Corrections 1. Install wiring listed for wet location where run through conduit outside. NM cable is not permitted. NEC 334.12 2. Need GFCI protection for new ac unit. NEC 210.8(F) 3. Phase white conductor of NM cable a phase color. 4. Condensate pump has to be installed as listed with cord plug connection, cord cap can not be cut off. Will need to replace cord end and install GFCI receptacle/switch for furnace. NEC 110.3 5. NM cable to be protected from ceiling to furnace disconnect. NEC 334.12 |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved October 06, 2026.