Permit 2608302

2814 ARLINGTON AVE · Filed 2026-09-29

Permit Details

TypeElectrical
Work Class003 Electrical New | WIRE NEW STRUCTURE 0
StatusActive
Work DoneWIRE NEW STRUCTURE 0
NotesNot on file
OwnerREYNA
ContractorSELF
Contractor PhoneN/A

Inspection History

DateInspectorTypeResultComment
2026-09-30 01:49:00 KJG E02 - Service Rejected OH feeder from house to detached garage - #2 al feeding 100A 3R main breaker panel at detached garage. Corrections 1. Overhead span needs to be supported to the mast on both house and detached garage. 2. OH conductors are not listed to be run down through conduit to the panels. 3. Need grounding electrode system at detached garage, will need 2 ground rods minimum 6' apart. 4. Roo flashing at the house needs to be installed so shingles overlap flashing down past roof penetration.
2026-09-30 01:50:00 KJG E04 - Rough-in Electrical Rejected Rough-in detached garage. Correction 1. NM cable to be run right angles to building lines. Per Pueblo ordinance.