Permit 2608302
2814 ARLINGTON AVE · Filed 2026-09-29
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003 Electrical New | WIRE NEW STRUCTURE 0 |
| Status | Active |
| Work Done | WIRE NEW STRUCTURE 0 |
| Notes | Not on file |
| Owner | REYNA |
| Contractor | SELF |
| Contractor Phone | N/A |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-09-30 01:49:00 | KJG | E02 - Service | Rejected | OH feeder from house to detached garage - #2 al feeding 100A 3R main breaker panel at detached garage. Corrections 1. Overhead span needs to be supported to the mast on both house and detached garage. 2. OH conductors are not listed to be run down through conduit to the panels. 3. Need grounding electrode system at detached garage, will need 2 ground rods minimum 6' apart. 4. Roo flashing at the house needs to be installed so shingles overlap flashing down past roof penetration. |
| 2026-09-30 01:50:00 | KJG | E04 - Rough-in Electrical | Rejected | Rough-in detached garage. Correction 1. NM cable to be run right angles to building lines. Per Pueblo ordinance. |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved October 01, 2026.