2211 NORTH DR · Filed 2026-09-04
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Active - Flagged |
| Work Done | A/C Hookup |
| Notes | AC Replacement |
| Owner | Rob Newman |
| Contractor | ATC HEATING LLC |
| Contractor Phone | Not on file |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-09-10 02:55:00 | KJG | E14 - AC Final - Electrical | Rejected | Installation of new ac unit replacement. Reinspection fee required for 2nd trip. Corrections 1. Install the smoke and carbon monoxide detectors per the IRC. IRC-R314 and R315 Need co detectors outside bedrooms within 15' of bedroom doors on both levels. 2. Breaker to be sized correctly to the condensing unit label. NEC - 440.12 (A) Max per unit is 30A. 3. Need GFCI protection installed per 210.8 (F) as of 9-01-2026 4. NM cable is not allowed to be install outside. NEC 334.12 There is NM cable in the whip to the unit. |
| 2026-09-10 03:34:00 | KJG | E14 - AC Final - Electrical | Rejected | Additional note to inspection 9-10-26 1. White conductor of NM cable feeding the disconnect needs to be phased a n phase color. |