4808 QUITA CT · Filed 2026-09-04
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Active - Flagged |
| Work Done | A/C Hookup |
| Notes | AC Hook up smokesCarbon in place service plug in place 35 amp Breaker at Disconnect |
| Owner | Bret Sutton |
| Contractor | GROUNDED ELECTRICAL LLC |
| Contractor Phone | 719-251-9154 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-09-10 01:35:00 | KJG | E14 - AC Final - Electrical | Rejected | Installation of new ac unit replacement and service receptacle. Reinspection fee required for 2nd trip. Corrections 1. Install the smoke and carbon monoxide detectors per the IRC. IRC-R314 and R315 Need smoke detector in basement bedroom. 2. Isolate neutral (Remove bond screw from neutral bus)and separate equipment grounds from neutral bus in disconnect (install an equipment ground bus). 3. GFCI protection require for outdoor outlet. NEC 210.8 (F) As of 9-01-2026 |