Permit 2607589
4 CHAUTARD CT · Filed 2026-09-04
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Active |
| Work Done | A/C Hookup |
| Notes | AC install |
| Owner | Eva Moldonado |
| Contractor | NATIVE ELECTRICAL CONTRACTORS |
| Contractor Phone | 719-339-7908 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-09-10 03:33:00 | JVD | E14 - AC Final - Electrical | Rejected | Installed a new AC condensing unit. Verified smokes/COs and service receptacle. Corrections: 1. Effective 09/01/26, AC condensing units are required to be GFCI protected. 210.8. 2. There is an open knockout in the back of the AC disconnect. 3. The breaker installed in the panel is a Eaton classified breaker. Must have cut sheet with panel compatibility on site or install GE/ABB breaker (GFCI). |