Permit 2607487
2949 ASTER ST · Filed 2026-09-01
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | Service |
| Status | Active |
| Work Done | Service |
| Notes | Water Heater Circuit and Disconnect |
| Owner | Philip Colby |
| Contractor | NICE SPRINGS LLC |
| Contractor Phone | Not on file |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-09-10 02:12:00 | JVD | E08 - Electric Final | Rejected | The water heater installed requires a 40 amp breaker and 40 amp conductors. It has 6000 watt heating elements. Also, a switched light is required in the vicinity of the equipment. |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved September 12, 2026.