Permit 2607485
3729 DEVONSHIRE LN · Filed 2026-09-01
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Has Final |
| Work Done | A/C Hookup |
| Notes | We will have to run the wiring and conduit around to the east side of the home this will be approximately 30 feet possibly 40 feet where we will attach it to the quick disconnect and tie the electrical whip into the condensing unit |
| Owner | Robert Cunningham |
| Contractor | PATTERSON PLUMBING & HEATING INC. |
| Contractor Phone | 719-544-4922 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-09-02 01:43:00 | JVD | E14 - AC Final - Electrical | Rejected | Installed a new AC condensing unit. Verified smokes/COs and service receptacle within 25' of the unit. Correction: Effective 09/01/26 the exemption for GFCI protection of an AC condensing unit expired. GFCI protection is required for all AC condensing units. NEC 210.8. |
| 2026-09-04 10:50:00 | JVD | E14 - AC Final - Electrical | Final | Correction has been made. Final electrical for AC install is approved. |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved September 12, 2026.