Permit 2607424

5527 BELLAGIO WAY · Filed 2026-08-28

Permit Details

TypeElectrical
Work Class003 Electrical New | WIRE BASEMENT 0.00
StatusActive
Work DoneWIRE BASEMENT 0.00
NotesBASEMENT FINISH AND BATH REISSUE OF 2511209
OwnerTHERESA SANDOVAL
ContractorSELF
Contractor PhoneN/A

Inspection History

DateInspectorTypeResultComment
2026-08-31 01:31:00 JVD E02 - Service Rejected Finish remainder of basement. Corrections: 1. Need to meet the wall space requirements of 2', 6' and 12' NEC-210.52A 2. CO & SMOKE DETECTORS TO BE INSTALLED PER IRC. IRC-R314 and R315 3. Make-up all ground wires for inspection. SOCOBD Building policy
2026-09-03 11:16:00 JVD E04 - Rough-in Electrical Complete Basement finish to include 1 bedroom and a large open area. Corrections from previous inspection have been made. Rough electrical approved.