The Pueblo Ledger

Pueblo's public records, made public.

Permit 2607350

3507 CANTERBURY LN · Filed 2026-08-26

Permit Details

TypeElectrical
Work Class003R Electrical Other | Electrical Service
StatusHas Final
Work DoneElectrical Service
NotesService upgrade
OwnerAdam Harrison
ContractorRED CROW ELECTRIC LTD
Contractor Phone719-248-5048

Inspection History

DateInspectorTypeResultComment
2026-08-31 02:14:00 JVD E02 - Service Rejected 200 amp overhead fed service upgrade. Feeds a new 100 amp subpanel inside the house back to back to old panel in kitchen that has been turned into a junction box. Verified cold water bond and smokes/COs are in place. Corrections: 1. There is an open 1-1/4" knockout in the back of the junction box with 2 nm cables run through it. 2. There is an open 1/2" knockout in the side of the junction box. 3. Drive the ground rods flush with the ground. 4. The conduit feeding the AC condensing unit appears to be at least partially supporting the GECs. 5. Need a separate permit for the AC connection.
2026-09-02 01:29:00 JVD E02 - Service Final All corrections from previous inspection have been made. Approved for reconnect. BHE
2026-09-02 13:29:00 JVD Z04 Release Sent to Utility Complete SFR service upgrade reconnect. -Utility Co: Black Hills; Service type: Overhead; Service size: 200A

Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved September 12, 2026.