Permit 2607350
3507 CANTERBURY LN · Filed 2026-08-26
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | Electrical Service |
| Status | Has Final |
| Work Done | Electrical Service |
| Notes | Service upgrade |
| Owner | Adam Harrison |
| Contractor | RED CROW ELECTRIC LTD |
| Contractor Phone | 719-248-5048 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-08-31 02:14:00 | JVD | E02 - Service | Rejected | 200 amp overhead fed service upgrade. Feeds a new 100 amp subpanel inside the house back to back to old panel in kitchen that has been turned into a junction box. Verified cold water bond and smokes/COs are in place. Corrections: 1. There is an open 1-1/4" knockout in the back of the junction box with 2 nm cables run through it. 2. There is an open 1/2" knockout in the side of the junction box. 3. Drive the ground rods flush with the ground. 4. The conduit feeding the AC condensing unit appears to be at least partially supporting the GECs. 5. Need a separate permit for the AC connection. |
| 2026-09-02 01:29:00 | JVD | E02 - Service | Final | All corrections from previous inspection have been made. Approved for reconnect. BHE |
| 2026-09-02 13:29:00 | JVD | Z04 Release Sent to Utility | Complete | SFR service upgrade reconnect. -Utility Co: Black Hills; Service type: Overhead; Service size: 200A |