Permit 2607334
1820 CEDAR ST · Filed 2026-08-26
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Active |
| Work Done | A/C Hookup |
| Notes | Install AC disconnect |
| Owner | Dorothy Vigil |
| Contractor | I & C POWER LLC |
| Contractor Phone | 870-588-1437 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-08-28 09:18:00 | JVD | E14 - AC Final - Electrical | Rejected | Installed a new AC condensing unit. Verified smokes/COs are in place. Corrections: 1. The AC disconnect is installed without proper working clearance as required by NEC 110.26. Note: Disconnect is not required as the main panel with the breaker for the condensing unit is within sight and within 50' of the unit. 2. There is a receptacle within 25' of the unit, however, the receptacle is unsafe and not code compliant. |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved September 12, 2026.