Permit 2607334

1820 CEDAR ST · Filed 2026-08-26

Permit Details

TypeElectrical
Work Class003R Electrical Other | A/C Hookup
StatusActive
Work DoneA/C Hookup
NotesInstall AC disconnect
OwnerDorothy Vigil
ContractorI & C POWER LLC
Contractor Phone870-588-1437

Inspection History

DateInspectorTypeResultComment
2026-08-28 09:18:00 JVD E14 - AC Final - Electrical Rejected Installed a new AC condensing unit. Verified smokes/COs are in place. Corrections: 1. The AC disconnect is installed without proper working clearance as required by NEC 110.26. Note: Disconnect is not required as the main panel with the breaker for the condensing unit is within sight and within 50' of the unit. 2. There is a receptacle within 25' of the unit, however, the receptacle is unsafe and not code compliant.