Permit 2607327
4602 190 N ELIZABETH ST · Filed 2026-08-26
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Has Final |
| Work Done | A/C Hookup |
| Notes | CU swap |
| Owner | Fed Ex |
| Contractor | GRAYC ELECTRIC, INC. |
| Contractor Phone | 719-352-7850 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-08-31 03:56:00 | KJG | E14 - AC Final - Electrical | Rejected | Installation of new ac unit. Correction 1. Install correct phase color wire, white wire is not allowed for phase wire. NEC 200.7 2. Chase nipple is not listed for grounding and bonding, can change to close nipple with 2 locknuts and p bushing. NEC 110.3 3. Install GFCI receptacle within 25' of unit. NEC 210.63 |
| 2026-09-02 01:50:00 | KJG | E14 - AC Final - Electrical | Final |