Permit 2607327

4602 190 N ELIZABETH ST · Filed 2026-08-26

Permit Details

TypeElectrical
Work Class003R Electrical Other | A/C Hookup
StatusHas Final
Work DoneA/C Hookup
NotesCU swap
OwnerFed Ex
ContractorGRAYC ELECTRIC, INC.
Contractor Phone719-352-7850

Inspection History

DateInspectorTypeResultComment
2026-08-31 03:56:00 KJG E14 - AC Final - Electrical Rejected Installation of new ac unit. Correction 1. Install correct phase color wire, white wire is not allowed for phase wire. NEC 200.7 2. Chase nipple is not listed for grounding and bonding, can change to close nipple with 2 locknuts and p bushing. NEC 110.3 3. Install GFCI receptacle within 25' of unit. NEC 210.63
2026-09-02 01:50:00 KJG E14 - AC Final - Electrical Final