Permit 2607312
1529 SPRUCE ST · Filed 2026-08-25
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | Service |
| Status | Has Final |
| Work Done | Service |
| Notes | Run power from inside panel to outside 30` away and set AC disc and whip into unit run a 20am convience outlet within 25` of condenser unit |
| Owner | Terri Harris |
| Contractor | I & C POWER LLC |
| Contractor Phone | 870-588-1437 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-09-02 11:08:00 | JVD | E14 - AC Final - Electrical | Rejected | Installed a new mini-split HVAC system. Verified smokes/COs and service receptacle. Correction: Maximum and minimum breaker size for this unit is 15 amps. A 30 amp breaker is installed. |
| 2026-09-10 12:13:00 | JVD | E14 - AC Final - Electrical | Final | Breaker has been replaced with a 15 amp breaker. Final electrical approved. |