Permit 2607009
1550 PIKE AVE · Filed 2026-08-13
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | Service |
| Status | Active |
| Work Done | Service |
| Notes | Service inspection & rough branch circuits installed by https:maps.app.goo.glnurJRRhYwYq1Sr8W9?g-st=i&utm-campaign=ac-im others |
| Owner | Lon Rathmel |
| Contractor | ALPHA & OMEGA ELECTRICAL SERVICES, LLC |
| Contractor Phone | 719-453-2921 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-08-14 01:45:00 | KJG | E04 - Rough-in Electrical | Rejected | Complete rewire /remodel of SFR single level with finished basement. Corrections 1. Missing receptacles for wall spacing north bedroom and basement living room. NEC 210.52(A) 2. Install circuit for future use in peninsula cabinet. NEC 210.52 (C)(2) 3. NM cable in basement to be 1 1/4" back from face of stud. NEC 300.4(D) 4. Install fan rated boxes in kitchen, living room, bedrooms on main level. NEC 314.27(C) 5. Remove unused EMT from metal boxes and plug holes in ceiling box in laundry room. 6. Install mud ring for dryer receptacle box. 7. All boxes to be made up. 8. Boxes in basement do not have enough cu.in. for box fill. NEC 314,16 9. Laundry circuit to be 20A circuit. NEC 210.11(C)(2) 10. NM cable is not allowed to be run through conduit outside. Will need to change wiring method from j-box to main panel. NEC 334.12 Note: Inspector talked to GC and told GC it was ok to cover wiring in kitchen. |