Permit 2606900
3223 CANTERBURY LN · Filed 2026-08-11
Permit Details
| Type | Mechanical |
|---|---|
| Work Class | 004R Mechanical Other | Replace A/C |
| Status | Has Final |
| Work Done | Replace A/C |
| Notes | Replacement of central air system. |
| Owner | Barbara Simmons |
| Contractor | ELMER`S SHEET METAL INC. |
| Contractor Phone | 719-566-8750 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-08-12 03:26:00 | TLC | M10 - AC Final | Final | |
| 2026-08-12 12:09:00 | JJG | M10 - AC Final | Rejected | breaker for condensing unit is to big unit call for 25amp minimum or 30amp max will accept photo send to 719-569-2901 there is a 40amp in panel |