The Pueblo Ledger

Pueblo's public records, made public.

Permit 2606855

4820 ROSECREST CT · Filed 2026-08-11

Permit Details

TypeElectrical
Work Class003R Electrical Other | A/C Hookup
StatusActive - Flagged
Work DoneA/C Hookup
NotesAC Swap-Whip Reconnect GFCi WR installed
OwnerLaura Wittrup
ContractorGROUNDED ELECTRICAL LLC
Contractor Phone719-251-9154

Inspection History

DateInspectorTypeResultComment
2026-08-12 12:49:00 JVD E14 - AC Final - Electrical Rejected Installed a new mini-split HVAC system. Added a service receptacle. Smokes/CO are in place. Corrections: 1. The AC disconnect is located behind the mini-split in violation of 110.26. 2. Gray is reserved for neutrals only. Must be a phase color. 200.7 3. The receptacle is required to be WR rated. Reinspection fee for 2nd trip added to permit.

Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved August 17, 2026.