Permit 2606767
2108 SETTLERS DR · Filed 2026-08-06
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Active |
| Work Done | A/C Hookup |
| Notes | AC Replacement |
| Owner | Sanford Glatzel |
| Contractor | ATC HEATING LLC |
| Contractor Phone | Not on file |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-08-10 12:38:00 | APB | E14 - AC Final - Electrical | Rejected | 1. NEED MAXIMUM OF 25 AMP OVERCURRENT DEVICE PER LISTING 110.3B AND 440. 2. NEED TO REPLACE THE SEALTITE AS IT IS DEGRADED AND CRACKED LOSING ITS LISTING OF WET LOCATION RATED. 3. NEED TO REPLACE WIRES INSIDE OF SEALTITE ALSO AS IT IS ROMEX, ROMEX IS NOT LISTED FOR A WET LOCATION. INTERIOR OF CONDUIT OUTSIDE IS A WET LOCATION. 300.9 4. NEED TO INSTALL CONNECTOR AND BACK OF DISCONNECT. FOR ROMEX ENTERING BACK OF DISCONNECT. 314.17 5.NEED TO REPLACE THE OUTSIDE A.C. DISCONNECT, DEGRADED AND HAS CRACKS. 110.3B. |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved August 17, 2026.