Permit 2606767

2108 SETTLERS DR · Filed 2026-08-06

Permit Details

TypeElectrical
Work Class003R Electrical Other | A/C Hookup
StatusActive
Work DoneA/C Hookup
NotesAC Replacement
OwnerSanford Glatzel
ContractorATC HEATING LLC
Contractor PhoneNot on file

Inspection History

DateInspectorTypeResultComment
2026-08-10 12:38:00 APB E14 - AC Final - Electrical Rejected 1. NEED MAXIMUM OF 25 AMP OVERCURRENT DEVICE PER LISTING 110.3B AND 440. 2. NEED TO REPLACE THE SEALTITE AS IT IS DEGRADED AND CRACKED LOSING ITS LISTING OF WET LOCATION RATED. 3. NEED TO REPLACE WIRES INSIDE OF SEALTITE ALSO AS IT IS ROMEX, ROMEX IS NOT LISTED FOR A WET LOCATION. INTERIOR OF CONDUIT OUTSIDE IS A WET LOCATION. 300.9 4. NEED TO INSTALL CONNECTOR AND BACK OF DISCONNECT. FOR ROMEX ENTERING BACK OF DISCONNECT. 314.17 5.NEED TO REPLACE THE OUTSIDE A.C. DISCONNECT, DEGRADED AND HAS CRACKS. 110.3B.