Permit 2606686
330 GAYLORD AVE · Filed 2026-08-05
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | Electrical Service |
| Status | Active |
| Work Done | Electrical Service |
| Notes | Service upgrade. |
| Owner | Scott |
| Contractor | L.J.I ELECTRIC |
| Contractor Phone | 719-369-8358 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-08-10 11:19:00 | JVD | E02 - Service | Rejected | 200 amp overhead fed service upgrade on a SFR. Verified 2 ground rods, cold water bond and smokes/COs are in place. Corrections: 1. Need to install a panel schedule. NEC-408.4A (Once power is restored to the house, will require this.) 2. Roof jack must be install per the manufacture instructions. NEC-110.3 and IRC-905.2.8.4 Unable to see the roof flashing. Supply either a ladder or send pictures of the install. 3. Need to identify and group multi-wire branch circuits. 4. The multi-wire branch circuits require either a handle tie for adjacent breakers or a 2-pole breaker. |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved August 17, 2026.