330 GAYLORD AVE · Filed 2026-08-05

Permit Details

TypeElectrical
Work Class003R Electrical Other | Electrical Service
StatusActive
Work DoneElectrical Service
NotesService upgrade.
OwnerScott
ContractorL.J.I ELECTRIC
Contractor Phone719-369-8358

Inspection History

DateInspectorTypeResultComment
2026-08-10 11:19:00 JVD E02 - Service Rejected 200 amp overhead fed service upgrade on a SFR. Verified 2 ground rods, cold water bond and smokes/COs are in place. Corrections: 1. Need to install a panel schedule. NEC-408.4A (Once power is restored to the house, will require this.) 2. Roof jack must be install per the manufacture instructions. NEC-110.3 and IRC-905.2.8.4 Unable to see the roof flashing. Supply either a ladder or send pictures of the install. 3. Need to identify and group multi-wire branch circuits. 4. The multi-wire branch circuits require either a handle tie for adjacent breakers or a 2-pole breaker.