Permit 2606668
310 SPRING ST · Filed 2026-08-05
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Active |
| Work Done | A/C Hookup |
| Notes | Need to disconnect the electrical from the old HVAC and connect it to the new HVAC |
| Owner | NICK MARTINEZ |
| Contractor | JETSON HOME CORPORATION |
| Contractor Phone | 888-996-5876 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-08-12 09:34:00 | KJG | E14 - AC Final - Electrical | Rejected | Installation of new ac/heat pump and air handler. Corrections 1. Breaker to be sized correctly to the condensing unit label. NEC - 440.12 (A) 2. A convenience receptacle/GFCI to be located within 25' of the condensing unit and on same level. NEC 210.63 |