736 WILSON AVE · Filed 2026-08-05

Permit Details

TypeElectrical
Work Class003R Electrical Other | Service
StatusActive
Work DoneService
NotesReplacing panel to make room for future heat pump install. Heat pump permit already issued Permit #2606631
OwnerJason Armijo
ContractorJETSON HOME CORPORATION
Contractor Phone888-996-5876

Inspection History

DateInspectorTypeResultComment
2026-08-07 09:45:00 JVD E02 - Service Rejected 200 amp overhead fed service upgrade on a SFR. Main panel feeds a full sized subpanel in the laundry room. Verified 2 ground rods and smokes/COs are in place. Corrections: 1. Install surge protection. NEC-230.67 2. The cold water bond has been run to the gas line. Need to remove from gas line. Incoming water line is plastic. 3. The subpanel in the laundry/utility room is in violation of 110.26 as there is a shelf above it and a dryer vent line below it. 4. Remove old GEC from subpanel.

Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved August 17, 2026.