Permit 2606584
736 MOFFAT ST · Filed 2026-08-03
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | Electrical Service |
| Status | Has Final |
| Work Done | Electrical Service |
| Notes | UPGRADE SERVICE TO 125-AMP PANEL |
| Owner | KRASKA AND YOUNG |
| Contractor | ROYAL ELECTRICAL SERVICES INC. |
| Contractor Phone | 719-546-0442 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-08-05 10:01:00 | JVD | E02 - Service | Rejected | 100 amp overhead fed service upgrade on a SFR. Main panel feeds a 60 amp subpanel in the basement. Turned old panel inside the house into a junction box. Verified 2 ground rods. Corrections: 1. Bond to incoming metallic waterline within 5ft of entering the structure. NEC-250.53D (There is a #6 run through the basement, could not tell where it starts or ends. Also, it has a splice with a split bolt and is run through EMT that would have to be bonded at both ends of the conduit run. 2. Install the smoke and carbon monoxide detectors per the IRC. IRC-R314 and R315 3. The cover for the junction box is not thick enough to meet the requirement of 314.101 |
| 2026-08-10 09:39:00 | JVD | Z04 Release Sent to Utility | Complete | SFR service upgrade reconnect. -Utility Co: Black Hills; Service type: Overhead; Service size: 100A |
| 2026-08-10 09:39:00 | JVD | E02 - Service | Final | Corrections from previous inspection have been made. Approved for reconnect. BHE |