The Pueblo Ledger

Pueblo's public records, made public.

Permit 2606583

1633 E 3RD ST · Filed 2026-08-03

Permit Details

TypeElectrical
Work Class003R Electrical Other | Service
StatusActive
Work DoneService
NotesREPAIR RISER FROM STORM DAMAGE
OwnerGLORIA BURCIAGA
ContractorROYAL ELECTRICAL SERVICES INC.
Contractor Phone719-546-0442

Inspection History

DateInspectorTypeResultComment
2026-08-04 09:17:00 KJG E18 - Mast/Meter Repair Rejected Mast repair only, new mast and service entrance conductors Corrections 1. Need a through bolt for connection point for utility service drop. 2. Existing GEC is just twisted together below the panel.. will need to crimp

Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved August 17, 2026.