Permit 2606370
30 MACGREGOR RD · Filed 2026-07-27
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | Service |
| Status | Active |
| Work Done | Service |
| Notes | Service upgrade and wire new ac |
| Owner | Barrera |
| Contractor | ROYSE ELECTRIC CO |
| Contractor Phone | 719-542-2011 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-07-31 11:30:00 | KJG | E02 - Service | Rejected | BHE. OH service upgrade, 200A meter panel combo feeding existing circuits of home through old panel/j-box. Correction 1. Group ungrounded conductors with neutral of multiwire branch circuits in old panel/j-box. Where more than one neutral conductor associated with different circuits is in an enclosure, grounded circuit conductors of each circuit shall be identified or grouped to correspond with the ungrounded circuit conductor(s) by wire markers, cable ties, or similar means in at least one location within the enclosure. NEC 200.4 Will accept photo within 5 day through socobd website. |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved August 03, 2026.