Permit 2606269
1227 S PRAIRIE AVE · Filed 2026-07-22
Permit Details
| Type | Miscellaneous |
|---|---|
| Work Class | 008 Misc. Fee. | SPECIAL INSPECTIONS 110.25 |
| Status | Active |
| Work Done | SPECIAL INSPECTIONS 110.25 |
| Notes | SPECIAL INSPECTION CHANGE OF OWNER |
| Owner | THE FALLOUT |
| Contractor | SELF |
| Contractor Phone | N/A |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-07-28 09:27:00 | DJM | X07 - Special Inspection | Rejected | Need proper air gaps on all drains in bar and kitchen area, need trap protection in public bathrooms and need permit and blue prints to new grease trap being added in kitchen area prints must go through plan review. |
| 2026-07-28 09:31:00 | TLC | X07 - Special Inspection | Rejected | 1) need licensed contractor to fix exhaust fans for bathrooms will need permit in place if exhaust fan needs changed out,will not need permit if its just repair work 2) section out of IFGC 411.1.1 commercial cooking appliances,need to tether fryer and cook top that are on casters |
| 2026-07-28 09:38:00 | JVD | X07 - Special Inspection | Rejected | All OK except that there is a broken receptacle plate in the kitchen north dishwashing area east wall. Also, there is a missing blank cover plate in the ceiling west end of the main room. |
| 2026-07-28 10:42:00 | DDK | X07 - Special Inspection | Rejected | Need second exit sign operational. |