Permit 2606255

2125 VINEWOOD LN · Filed 2026-07-22

Permit Details

TypeElectrical
Work Class003R Electrical Other | Service
StatusActive
Work DoneService
NotesSERVICE UPGRADE TO 200 AMPS 1 MINI SPLIT INSTALL
OwnerMARY SANCHEZ
ContractorI & C POWER LLC
Contractor Phone870-588-1437

Inspection History

DateInspectorTypeResultComment
2026-07-28 12:12:00 JVD E02 - Service Rejected 200 amp overhead fed service upgrade on a SFR. Verified 2 ground rods. Meter/panel combo feeding an existing subpanel back to back inside the residence. Corrections: 1. Need to install smokes/COs per IRC R314 and R315. 2. The cold water bond is required to be made within 5' of the main water line entering the structure. 3. There are 4 multi-wire branch circuits in the subpanel that need to be installed on either a 2 pole breaker or on adjacent phases with handle ties. 4. GEC not allowed to be supported with EMT or water lines, line sets, etc.
2026-07-28 12:12:00 JVD E14 - AC Final - Electrical Rejected Installed a new mini-split HVAC system. Verified service receptacle. Correction: Need to install smokes/COs per IRC R314 and R315. a service receptacle.