Permit 2606255
2125 VINEWOOD LN · Filed 2026-07-22
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | Service |
| Status | Active |
| Work Done | Service |
| Notes | SERVICE UPGRADE TO 200 AMPS 1 MINI SPLIT INSTALL |
| Owner | MARY SANCHEZ |
| Contractor | I & C POWER LLC |
| Contractor Phone | 870-588-1437 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-07-28 12:12:00 | JVD | E02 - Service | Rejected | 200 amp overhead fed service upgrade on a SFR. Verified 2 ground rods. Meter/panel combo feeding an existing subpanel back to back inside the residence. Corrections: 1. Need to install smokes/COs per IRC R314 and R315. 2. The cold water bond is required to be made within 5' of the main water line entering the structure. 3. There are 4 multi-wire branch circuits in the subpanel that need to be installed on either a 2 pole breaker or on adjacent phases with handle ties. 4. GEC not allowed to be supported with EMT or water lines, line sets, etc. |
| 2026-07-28 12:12:00 | JVD | E14 - AC Final - Electrical | Rejected | Installed a new mini-split HVAC system. Verified service receptacle. Correction: Need to install smokes/COs per IRC R314 and R315. a service receptacle. |