Permit 2606244

2318 THATCHER AVE · Filed 2026-07-21

Permit Details

TypeMiscellaneous
Work Class008 Misc. Fee. | SPECIAL INSPECTIONS 110.25
StatusActive
Work DoneSPECIAL INSPECTIONS 110.25
NotesSPECIAL CHANGE IN USE BARBER SHOP NO CONSTRUCTION
OwnerAWREDDY BARBER SUPPLY
ContractorSELF
Contractor PhoneN/A

Inspection History

DateInspectorTypeResultComment
2026-07-23 09:38:00 JVD X07 - Special Inspection Rejected 1. There's an open knockout on the deadfront in the main subpanel. 2. Need to GFCI protect all of the receptacles in the bathroom. 3. The receptacle next to the subpanel has reversed polarity. 4. The exit sign is hanging by the wires. 5. There's a blank cover on the ceiling that is hanging down and needs to be reattached to the ceiling. 6. Need to complete the panel schedule.
2026-07-23 09:44:00 DJM X07 - Special Inspection Rejected Need permit and licensed contractor for water heater that was installed must fix code violations for water heater pan, T&P discharge, bottom fed water heater and need mixing valve on LAV and toilet seat must be open front less cover.
2026-07-23 09:46:00 TLC X07 - Special Inspection Rejected 1) need licensed contractor to pull permits for mini splits that were installed 2) bath fan in bathroom is not working needs to work with lights
2026-07-23 09:50:00 RLO X07 - Special Inspection Rejected Building division did pass fire-protection and egress requirements, will need all 3 MEP's permits for corrections, see notes from each disciplines. Photo's to file. Special inspection is rejected till permitted inspections are final out.

Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved August 03, 2026.