Permit 2606187
2 COVINA CT · Filed 2026-07-20
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Active |
| Work Done | A/C Hookup |
| Notes | Air Handler Replacement |
| Owner | Mike Henderson |
| Contractor | R BUCK HEATING, COOLING, PLUMBING & ELEC |
| Contractor Phone | 805-512-3738 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-07-23 10:39:00 | JVD | E14 - AC Final - Electrical | Rejected | Replaced an existing AC condensing unit and air handling unit in the attic. Verified smokes/COs and outside service receptacle for the condensing unit. Corrections: 1. The pvc coated MC cable in the attic is not properly supported/secured. 330.30 2. Need service receptacle in the attic within 25' of the air handling unit. 210.63 3. The pvc conduit running to the AC condensing unit needs an expansion coupling. 352.44 4. The pvc conduit running to the AC condensing unit is tapped into a pvc LB violating the listing of the LB. 110.3 |