Permit 2606184
4911 BRIARCREST DR · Filed 2026-07-20
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Has Final |
| Work Done | A/C Hookup |
| Notes | AC Replacement |
| Owner | Larry Bontrager |
| Contractor | R BUCK HEATING, COOLING, PLUMBING & ELEC |
| Contractor Phone | 805-512-3738 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-07-27 01:59:00 | JVD | E14 - AC Final - Electrical | Rejected | Replaced an existing AC condensing unit. Verified smokes/COs and service receptacle. Corrections: 1. Need to install a bushing in the back of the disconnect. 2. Need to reidentify the white conductor in the NM cable in the disconnect to a phase color. 3. Need to strap the liquitite conduit within 12" of the AC disconnect. |
| 2026-07-30 10:05:00 | JVD | E14 - AC Final - Electrical | Final | Corrections from previous inspection have been made. Final electrical approved. |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved August 03, 2026.