Permit 2606182
1911 TORONTO ST · Filed 2026-07-20
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Has Final |
| Work Done | A/C Hookup |
| Notes | AC Replacement |
| Owner | Rafeal Snowden |
| Contractor | R BUCK HEATING, COOLING, PLUMBING & ELEC |
| Contractor Phone | 805-512-3738 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-07-21 11:32:00 | JVD | E14 - AC Final - Electrical | Rejected | Replaced an existing AC condensing unit. Verified smokes/COs and service receptacle. Correction: The wiring from the AC disconnect to the condensing unit is NM cable and not listed for use in a wet location. 334.12 |
| 2026-07-27 01:12:00 | JVD | E14 - AC Final - Electrical | Rejected | According to the owner, the corrections have not been made. Reinspection fee required. |
| 2026-07-31 12:43:00 | JVD | E14 - AC Final - Electrical | Final | Correction from previous inspection has been made. Final electrical approved. |