Permit 2605732
224 S UNION AVE · Filed 2026-07-08
Permit Details
| Type | Miscellaneous |
|---|---|
| Work Class | 008 Misc. Fee. | SPECIAL INSPECTIONS 110.25 |
| Status | Active |
| Work Done | SPECIAL INSPECTIONS 110.25 |
| Notes | SPECIAL INSPECTION HEAVENLY SOUL PLATES |
| Owner | PUEBLO PATRIARCHS LIMITED |
| Contractor | SELF |
| Contractor Phone | N/A |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-07-09 09:26:00 | JAM | X07 - Special Inspection | Complete | |
| 2026-07-09 09:32:00 | FDR | X07 - Special Inspection | Complete | all plumbing is compliant. |
| 2026-07-09 09:50:00 | KJG | X07 - Special Inspection | Rejected | There is a cord for equipment in kitchen going through wall into closet. Cords are not allowed to be run through walls. NEC 400.12 Receptacle can be on same side of wall as equipment but will allow if wall has complete pass through for access and cord is not penetrating through a hole in the wall. |
| 2026-07-09 09:59:00 | RLO | X07 - Special Inspection | Rejected | Disciplines HVAC/Mechanical and Plumbing passed inspection. Building and electrical are for the same issue need a opening in the closet basement kitchen area, need a top 2x4 installed across the studs and 5/8 sheetrock on all 4 side installed, once completed re-call for building final. This opening is for the cord going through the wall plugging into this outlet, making a passage that is protected for the cord plugin. |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved July 11, 2026.