Permit 2605725

3534 DELANO CT · Filed 2026-07-07

Permit Details

TypeBuilding
Work Class438 Res. Garage | DETACHED GARAGE/UNFIN. STORAGE 208
StatusActive
Work DoneWire New Structure
NotesNot on file
OwnerKOSHAK
ContractorRUFF 2 FINISH CONSTRUCTION LLC
Contractor Phone7194600433

Inspection History

DateInspectorTypeResultComment
2026-03-06 11:31:00 JVD E03 - Underground Rejected Electrical and gas lines are allowed in the same trench provided that at least 6" of separation are maintained at all times. Per mechanical code.
2026-04-30 01:50:00 JVD E03 - Underground Partial Underground conduits around perimeter of new in ground pool. Multiple 1" pvc conduits are approved to cover. They run to the west to the location of the future equipment.
2026-04-30 01:51:00 JVD E13 - Pool Grounding Partial Perimeter pool bonding for in ground metal pool. 4 corners and cups. Approved.
2026-06-11 12:00:00 JVD E13 - Pool Grounding Complete Pool deck bonding including all 4 corners, cups and pool cover on both ends. Approved.
2026-06-29 10:48:00 APB E08 - Electric Final Rejected NEED PERMIT FOR POOL BUILDING AND WIRING OF POOL BUILDING. THIS PERMIT IS FOR THE POOL AND IT'S EQUIPMENT ONLY.
2026-07-10 01:12:00 JVD E02 - Service Complete Added a 100 amp underground fed subpanel on the east outside wall of a new poolhouse with 2 ground rods.
2026-07-10 01:12:00 JVD E04 - Rough-in Electrical Rejected The conductors to the high outlet box in the west end south wall of the equipment room are run on the backside of the box violating the NEC 334.4D Upload a picture of the correction within 5 days. This is a rough in for a new pool house at a SFR.
2026-06-05 10:09:00 WRR P08 - Rough-In Plumbing Complete pool house rough in no permit card found
2026-07-02 12:18:00 DLJ P08 - Rough-In Plumbing Complete On pool house bathroom
2026-07-08 11:18:00 DDK B04 - Frame Complete Will need foundation certificate before final inspection.
2026-07-09 01:43:00 JVD E16 - Pool Final Rejected 1. All components must be in place for final inspection. Missing the 9 square inches of metal in contact with the water. 2. All equipment to be GFCI protected. NEC 680.32 3. All equipment/conductive surfaces to be bonded. NEC 680.26 Missing 9" square metal in contact with the water.

Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved July 11, 2026.