Permit 2605607
4911 BUTTE LN · Filed 2026-07-06
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Active |
| Work Done | A/C Hookup |
| Notes | AC Replacement |
| Owner | George Juarros |
| Contractor | ATC HEATING LLC |
| Contractor Phone | Not on file |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-07-06 02:09:00 | KJG | E14 - AC Final - Electrical | Rejected | Installation of new ac unit replacement. Corrections 1. Install the smoke and carbon monoxide detectors per the IRC. IRC-R314 and R315 2. Breaker to be sized correctly to the condensing unit label. NEC - 440.12 (A) Unit max breaker is 15A there is a 30A installed. 3. NM cable is not listed to be run outside, there is NM cable run in whip to AC unit. NEC 334.12 4. Need to phase white conductor a phase color of NM cable on line side of disconnect. 5. Need proper clearance in front of disconnect. NEC 440.14 |