Permit 2605607

4911 BUTTE LN · Filed 2026-07-06

Permit Details

TypeElectrical
Work Class003R Electrical Other | A/C Hookup
StatusActive
Work DoneA/C Hookup
NotesAC Replacement
OwnerGeorge Juarros
ContractorATC HEATING LLC
Contractor PhoneNot on file

Inspection History

DateInspectorTypeResultComment
2026-07-06 02:09:00 KJG E14 - AC Final - Electrical Rejected Installation of new ac unit replacement. Corrections 1. Install the smoke and carbon monoxide detectors per the IRC. IRC-R314 and R315 2. Breaker to be sized correctly to the condensing unit label. NEC - 440.12 (A) Unit max breaker is 15A there is a 30A installed. 3. NM cable is not listed to be run outside, there is NM cable run in whip to AC unit. NEC 334.12 4. Need to phase white conductor a phase color of NM cable on line side of disconnect. 5. Need proper clearance in front of disconnect. NEC 440.14