Permit 2605605
1710 BERKLEY AVE · Filed 2026-07-06
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | A/C Hookup |
| Status | Active |
| Work Done | A/C Hookup |
| Notes | AC Replacement |
| Owner | Richard Alvidrez |
| Contractor | ATC HEATING LLC |
| Contractor Phone | Not on file |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-07-06 10:49:00 | JVD | E14 - AC Final - Electrical | Rejected | 1. Install the smoke and carbon monoxide detectors per the IRC. IRC-R314 and R315 (Outside both sets of bedrooms within 15' and in bsmt.) 2. Conduit to be properly secured/fastened. Per Article 300 for type used (Flex from AC disconnect to condensing unit.) 3. Panel breaker to be properly labeled. NEC- 408.4 4. Correct wiring method to be used. Per article 300 and type of wiring method used. (NM cable not allowed outside in wet location.) Replaced existing AC condensing unit. |