Permit 2605605

1710 BERKLEY AVE · Filed 2026-07-06

Permit Details

TypeElectrical
Work Class003R Electrical Other | A/C Hookup
StatusActive
Work DoneA/C Hookup
NotesAC Replacement
OwnerRichard Alvidrez
ContractorATC HEATING LLC
Contractor PhoneNot on file

Inspection History

DateInspectorTypeResultComment
2026-07-06 10:49:00 JVD E14 - AC Final - Electrical Rejected 1. Install the smoke and carbon monoxide detectors per the IRC. IRC-R314 and R315 (Outside both sets of bedrooms within 15' and in bsmt.) 2. Conduit to be properly secured/fastened. Per Article 300 for type used (Flex from AC disconnect to condensing unit.) 3. Panel breaker to be properly labeled. NEC- 408.4 4. Correct wiring method to be used. Per article 300 and type of wiring method used. (NM cable not allowed outside in wet location.) Replaced existing AC condensing unit.