Permit 2605505
105 E RIVERWALK · Filed 2026-06-30
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | Wire HVAC |
| Status | Has Final |
| Work Done | Wire HVAC |
| Notes | WIRING RTU |
| Owner | Angelo`s Pizzeria |
| Contractor | ROYAL ELECTRICAL SERVICES INC. |
| Contractor Phone | 719-546-0442 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-07-01 09:47:00 | KJG | E14 - AC Final - Electrical | Rejected | Installation of new RTU replacement. Corrections 1. Label disconnect with source and circuit. NEC 110.22 2. Install green conductor, Conductors smaller than #4 can not be rephase as an equipment ground. NEC 250.119 |
| 2026-07-06 09:51:00 | KJG | E14 - AC Final - Electrical | Final | Corrections made per previous inspection notes. |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved July 11, 2026.