Permit 2605474

70 MACNAUGHTON RD · Filed 2026-06-29

Permit Details

TypeMechanical
Work Class004R Mechanical Other | Replace Furnace
StatusActive - Flagged
Work DoneReplace Furnace
NotesFurnace Replacement
OwnerMario Factor
ContractorATC HEATING LLC
Contractor PhoneNot on file

Inspection History

DateInspectorTypeResultComment
2026-07-01 02:27:00 JAM M18 - Furnace Final Rejected does not meet code $100 reinspection fee is issued - flue vent termination doesn't meet manufactures required clearances to building openings, vent termination must point away from structure (protection of building structure), insufficient vent pipe support
2026-07-10 11:26:00 JAM M18 - Furnace Final Rejected does not meet code, $100 reinspection fee is issued - IFGC 502.5 support of vents - exterior vent has been changed and requires support (interior vent support has been completed, ok to cover)