Permit 2605452

603 VAN BUREN ST · Filed 2026-06-29

Permit Details

TypeElectrical
Work Class003R Electrical Other | A/C Hookup
StatusActive
Work DoneA/C Hookup
NotesAC Replacement
OwnerColleen Maxwell
ContractorR BUCK HEATING, COOLING, PLUMBING & ELEC
Contractor Phone805-512-3738

Inspection History

DateInspectorTypeResultComment
2026-07-07 02:24:00 APB E14 - AC Final - Electrical Rejected 1. NEED THE LISTING PAPER FOR THE CLASSIFIED BREAKER TO VERIFY IT LISTED FOR THE PANEL IN WHICH IT WAS INSTALL. 110.3B 2. NEED TO LABEL THE PANEL. 408.4 3. NEED WET LOCATION RATED FITTINGS FROM THE JBOX OUTSIDE TO THE AC DISCONNECT. FITTING INSTALLED ARE DRY RATED ONLY.