325 VAN BUREN ST · Filed 2026-06-26
Permit Details
| Type | Electrical |
|---|---|
| Work Class | 003R Electrical Other | UPGRADE REPLACE SERVICE 1 0 |
| Status | Active |
| Work Done | UPGRADE REPLACE SERVICE 1 0 |
| Notes | SERVICE UPGRADE 100 TO 200 |
| Owner | AARON HEIZER |
| Contractor | LARRY`S ELECT. & REFRIG. INC. |
| Contractor Phone | 719-543-2135 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-06-30 08:41:00 | APB | E02 - Service | Rejected | 1. NEED TO REMOVE THE GEC FROM THE WIREWAY FOR AN UNDERGOUND SERVICE, CANNOT HAVE ANY WIRES IN THIS CHASE AS THIS IS PART OF THE METER ENCLOSURE PER LISTING. 2. NEED TO VERIFY 2 GROUND RODS. 3. NEED GEC TO WATER LINE OR VERIFY WATERLINE IS PLASTIC. 4.NEED ACCESS TO INTERIOR, NOBODY HOME AT TIME OF INSPECTION. 5. WILL NEED TO REMOVE OLD SERVICE MAST AND METER AFTER NEW SERVICE IS RELEASED. 6. ARE WE USING THE OLD SERVICE PANEL AS JBOX ? INSPECTOR WILLING TO MEET CONTRACTOR ON JOBSITE IF NEEDED. |
| 2026-07-09 09:40:00 | JVD | E02 - Service | Partial | Overhead fed service upgrade on a detached garage. Verified 2 ground rods, cold water line bond. Approved for power/meter swap to new service. BHE Notes: 1. Replace receptacles under the panel with TR/WR rated receptacle and GFCI receptacle. 2. Finish connecting the subpanel next to the main panel once power has been swapped. 3. Remove old meter/riser once power is swapped. Call for a final inspection once all above listed items have been completed. |
Source: Pueblo Regional Building Department. PRBD transitioned to the Southern Colorado Building Department in January 2026 — verify current status at socobd.com. Retrieved July 11, 2026.