Permit 2605406
1 DEER RUN CT · Filed 2026-06-26
Permit Details
| Type | Mechanical |
|---|---|
| Work Class | 004R Mechanical Other | Replace Furnace |
| Status | Has Final |
| Work Done | Replace Furnace |
| Notes | Furnace replacement went from an eighty to a ninety percent flu pipe is ran through the attic |
| Owner | Reality team |
| Contractor | BREATHE EASY AIR LLC |
| Contractor Phone | 719-505-3360 |
Inspection History
| Date | Inspector | Type | Result | Comment |
|---|---|---|---|---|
| 2026-06-26 10:51:00 | JAM | M18 - Furnace Final | Rejected | Does not meet code, $100 reinspection fee is issued - IFGC M306.1 Access for maintenance and replacement - Electronic air cleaner components are not accessible, IFGC 307.2 Fuel-burning appliances - 1% grade minimum for horizontal piping for condensate includes flue vent (vent in attic does not have proper grade) and IFGC 503.9 and manufacturer's installation instructions, IFGC 503.16 outside wall penetrations - must be sealed, IFGC 408.4 Sediment trap - required after gas shut off by appliance |
| 2026-06-29 02:42:00 | JAM | M18 - Furnace Final | Final |