Permit 2605406

1 DEER RUN CT · Filed 2026-06-26

Permit Details

TypeMechanical
Work Class004R Mechanical Other | Replace Furnace
StatusHas Final
Work DoneReplace Furnace
NotesFurnace replacement went from an eighty to a ninety percent flu pipe is ran through the attic
OwnerReality team
ContractorBREATHE EASY AIR LLC
Contractor Phone719-505-3360

Inspection History

DateInspectorTypeResultComment
2026-06-26 10:51:00 JAM M18 - Furnace Final Rejected Does not meet code, $100 reinspection fee is issued - IFGC M306.1 Access for maintenance and replacement - Electronic air cleaner components are not accessible, IFGC 307.2 Fuel-burning appliances - 1% grade minimum for horizontal piping for condensate includes flue vent (vent in attic does not have proper grade) and IFGC 503.9 and manufacturer's installation instructions, IFGC 503.16 outside wall penetrations - must be sealed, IFGC 408.4 Sediment trap - required after gas shut off by appliance
2026-06-29 02:42:00 JAM M18 - Furnace Final Final